ELECTRONIC RCBO JEL4A 6kA 2P 32A/30mA

Disponibile

COD: 00800 Categorie: ,

Descrizione

INTERRUTTORE DIFFERENZIALE magnetotermico A DUE POLI 

CARATTERISTICHE TECNICHE

  • TipoA
  • ModelloJEL4A
  • Tensione nominale240 V
  • Corrente nominale32 A
  • Capacità di interruzione6 kA
  • Numero dei poli1
  • Corrente di dispersione30mA
  • TipoRCBO
  • Dimensione complessiva (mm)L:78/W:36/H:81

     

    DESCRIPTION OF THE OPERATING SYSTEM »
    RCBO JEL4A is with enhanced sensibility and fast – operating protection devices applicable in circuits with
    harmonic or direct pulsating current component presence.
    “Phase line + neutral + leakage “protection circuit breaker JEL4A is applied to the single-phase residential
    circuit of 50Hz or 60Hz, rated voltage 230V, to protect leakage, civil electrical overload and short circuit. The
    product is provided with many advantages such as small size, high breaking capacity, cutting off zero-line,
    live line at the same time, and leakage protecting in the case of reverse wiring live line.

    TECHNICAL SPECIFICATION SHEET
    FUNCTIONS »
    ? Switching off heavy-loaded electrical circuits at short circuit or overload.
    ? Switching off heavy-loaded electrical circuits at insulation damage of the conductors to the consumers.
    ? Switching off heavy-loaded electrical circuits at presence of a person and animals under voltage.
    ? Switching off consumers at harmonic pres ence due to luminescent lights.
    ? Switching off consumers in DC circuits at fault currents presence.
    ? Used to protect not only particular consum ers/circuits, but also the whole panel.
    ? Remarkable with high reliability of current characteristics.
    ? Control: manual switching on and automatic switching off at failure in the insulation after the breaker.
    TECHNICAL DATA »
    ? Mode: Electronic
    ? Type: A for AC/DC current
    ? Rated operating voltage Ue: 230/240V 50/60 Hz
    ? Insulation voltage Ui: 500V
    ? Circuit breaker rated current: according to the table
    ? Residual current responsiveness: 30; 300mA
    ? Break time under I?n: ≤0.1s
    ? Circuit breaker tripping curve: C
    ? Energy limiting class: 3
    ? Breaking capacity: 6 000A
    ? Rated impulse withstand voltage (1.5/50)
    ? Uimp: ≥4000V
    ? Dielectric test voltage at ind.Freq. for 1min: 2kV
    ? Polution degree: 2
    ? Electrical life: 4 000 cycles
    ? Mechanical life: 10 000 cycles
    ? IP code: IP>20
    ? Indication for operating (switched on) position
    ? Terminal connection type: Cable
    ? Pin-type busbar
    ? U-type busbar
    ? Terminal size top/bottom for cable: 25mm2
    ? Terminal size top/bottom for busbar: 25 mm2
    ? Tightening torque: 2.5Nm
    ? Reference temperature for setting of thermal element: 30°C
    ? Ambient temperature: -10°C + 65°C
    ? Installation altitude: up to 2000 m

    TECHNICAL SPECIFICATION SHEET
    MOUNTING »
    ? On DIN-rail
    ? Mounting position: vertical the residual current device is mounted in the distribution box, and
    after the device the neutral conductor and the earthing conductor must not be connected
    together. In order to work accurately, the device must have a three- or five-conductor grid with
    separate operating neutral conductor (N) and separate protecting conductor (PE) (e.g., earthing
    system TN-S or TT with three or five conductors).